ADVANTECH ADAM-4115December 13, 2021
ADVANTECH ADAM-4115
Robust 6-Ch RTD Input Module
A RTD module is popular for temperature measurement. Unlike tranditional designs, the ADAM-4015 provides six RTD input channels for different types of RTD signal as an cost-effective solution in industrial & building automation. Occasionally, broken external wiring will lead to inaccurate current value. The ADAM-4015 provides a broken wiring detection function so users can easily troubleshoot broken wiring problems.
KEY FEATURES:
- Robust 6-Ch RTD Input Module
- Protocols:Modbus RTU,ASCII
- Watch dog to recover the system
- 3000VDC isolation protection
- Wiring burned-out detection function
Channels | Robust 6 RTD Input Module |
---|---|
Loop Number | – |
RTD Input Type | Pt, Balco, Ni and BA1 RTD |
Input Connections | 2, 3-wire |
RTD Types and Temperature Ranges | Pt100 : -50~150°C, 0~100°C, 0~200°C, 0~400°C, -200~200°C, Supports both IEC 60751 ITS90 (0.0385 W/W/°C) and JIS C 1604 (0.0392 W/W/°C) |
Input Impedance | 10 MΩ |
Accuracy | ±0.1% (Typical) |
Sampling Rate | 10 Hz total channels |
CMR @ 50/60 Hz | 120 dB |
NMR @ 50/60 Hz | – |
Span Drift | ± 25 ppm/°C |
Zero Drift | ±6 μV/° C |
Protection | – |
Certification | CE, FCC |
Power Consumption | Typical: 0.5 W @ 24 VDC, Max: 0.9 W @ 24 VDC |
Power Input | 10 ~ 48 VDC |
Operating Temperature | -40 ~ 85°C (-40 ~ 185°F) |
Storage Temperature | -40 ~ 85°C (-40 ~ 185°F) |
Operating Humidity | 5 ~ 95% RH |
Storage Humidity | – |