• ADVANTECH

ADVANTECH ADAM-4015

6RTD Modbus RS-485 Remote I/O

A RTD module is popular for temperature measurement. Unlike tranditional designs, the ADAM-4015 provides six RTD input channels for different types of RTD signal as an cost-effective solution in industrial & building automation. Occasionally, broken external wiring will lead to inaccurate current value. The ADAM-4015 provides a broken wiring detection function so users can easily troubleshoot broken wiring problems.
Add to WishlistAdd to Compare

KEY FEATURES:

  • 6ch RTD
  • Protocols:Modbus RTU,ASCII
  • Watch dog to recover the system
  • 3000VDC isolation protection
  • Wiring burned-out detection function
Amplicon Middle East-Advantech-ADAM-4015-1
Channels

6RTD Modbus RS-485 Remote I/O

Loop Number

RTD Input Type

Pt, Balco and Ni RTD

Input Connections

2, 3-wire

RTD Types and Temperature Ranges

Pt100 : -50~150°C, 0~100°C, 0~200°C, 0~400°C, -200~200°C, Supports both IEC 60751 ITS90 (0.0385 W/W/°C) and JIS C 1604 (0.0392 W/W/°C)
Pt1000 : -40~160°C
Balco (500) : -30~120°C
Ni (518) : -80~100°C, 0~100°C

Input Impedance

10 MΩ

Accuracy

±0.1% (Typical)

Sampling Rate

10/100 Hz total channels (selected by utility)

CMR @ 50/60 Hz

120 dB

NMR @ 50/60 Hz

Span Drift

± 25 ppm/°C

Zero Drift

±6 μV/° C

Protection

Certification

CE, FCC, UL

Power Consumption

1.2 W @ 24 VDC

Power Input

10 ~ 30 VDC

Operating Temperature

-10 ~ 70°C (14 ~ 158°F)

Storage Temperature

– 25 ~ 85°C (-13 ~ 185°F)

Operating Humidity

5 ~ 95% RH

Storage Humidity

Data Sheet

Download / View