ADVANTECH ADAM-5080December 13, 2021
ADVANTECH ADAM-5080
4-ch Counter/Frequency Module
With ADAM-5080 4-Channel Counter/Frequency Module, users can select either counter or frequency mode for data input. ADAM-5080 offers users flexible and versatile applications such as counter, frequency, alarm setting, Up / Down or Bi-direction Functions.
KEY FEATURES:
- Minimum Pulse Width: 500μ sec. (Frequency Mode), 100μ sec. (Counter Mode)
- Function Mode: Counter (Up/Down, Bi-direction) Frequency
- Input Frequency: Frequency Mode: 0.3~1000 Hz Counter Mode: 5000 Hz max.
- Isolated Voltage: 1000 VRMS
- Programmable Digital Noise Filter: 1~65000μ sec.
Channels | 4 x Counter/Frequency Module |
---|---|
Certification | CE, FM |
Enclosure | ABS+PC |
Power Consumption | 1.5 W (max.) |
Counter Aux. Function | Initial preset, hi-low alarm setting, alarm digital output mapping, overflag |
Input Frequency | 0.3 ~ 1,000 Hz max. (frequency mode), 5,000 Hz max. (counter mode) TTL only |
Input Level | Isolated or TTL level |
Isolation Input Level | Logic level 0: 1 VDC max, Logic level 1: 3.5 ~ 30 VDC |
Isolation Voltage | 1,000 VRMS |
Maximum Count | 4,294,967,295 (32 bits) |
Minimum Input Current | 2 mA (isolated) |
Minimum Pulse Width | 500 μs (frequency mode), 100 μs (counter mode) |
Modes | Counter (up/down, bi-direction), Frequency |
Programmable Digital Filter | 1 ~ 65,000 μsec (Noise Filter Function) |
TTL Input Level | Logic level 0: 0 ~ 0.8 VDC, Logic level 1: 2.3 ~ 5 VDC |